Also recognize VPN is only as secure as its connected devices.ĬISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.ĬISA also provides a section for control systems security recommended practices on the ICS webpage on.
When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Locate control system networks and remote devices behind firewalls, and isolate them from the business network. Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet. Siemens simatic his update#
Update the entire solution to TIA Portal v17 and use TLS communication using individual certificates between PLC, HMIs, and PG/PCįor more information about this vulnerability and the associated mitigations, please see SSA-434534ĬISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. System integrity: Configure, maintain, and protect devices by applying applicable compensating controls and using built-in security capabilities. Network security: Ensure PLC systems are not connected to untrusted networks. Plant security: Ensure physical prevention of access to critical components. Apply “defense in depth” as outlined on pages 12ff of the operational guidelines for industrial security, especially:.
Use the display to configure additional access protection of the S7-1500 CPU (This blocks remote client connections, even when the client can provide the correct password). Disallow client connections via the ENDIS_PW instruction of the S7-1200 or S7-1500 CPU (This blocks remote client connections, even when the client can provide the correct password). Siemens simatic his password#
Apply password protection for S7 communication. Siemens has identified the following specific workarounds and mitigations users can apply to reduce the risk: SIMATIC S7-PLCSIM Advanced: Update to v4.0 or later version. related ET200 CPUs and SIPLUS variants): Update to v2.9.2 or later version SIPLUS variants): Update to v4.5.0 or later version
SIMATIC Drive Controller family: Update to v2.9.2 or later version. Siemens simatic his software#
SIMATIC S7-1500 Software Controller: Update to v21.9 or later version. SIMATIC ET 200SP Open Controller CPU 1515SP PC2: Update to v21.9 or later version. Siemens is preparing further updates and recommends specific countermeasures for products where updates are not, or not yet available. Siemens has released updates for several affected products and recommends updating to the latest versions. Tal Keren from Claroty reported this vulnerability to Siemens. CRITICAL INFRASTRUCTURE SECTORS: Chemical, Critical Manufacturing, Energy, Food and Agriculture, Water and Wastewater Systems. A CVSS v3 base score of 8.1 has been calculated the CVSS vector string is ( AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H). Siemens simatic his code#
A remote, unauthenticated attacker with network access to Port 102/TCP could write arbitrary data and code to protected memory areas or read sensitive data to launch further attacks.ĬVE-2020-15782 has been assigned to this vulnerability.
SIMATIC S7-PLCSIM Advanced: All versions prior to v4.0Ĥ.2 VULNERABILITY OVERVIEW 4.2.1 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119Īffected devices are vulnerable to a memory protection bypass through a specific operation. SIMATIC S7-1500 Software Controller: All versions. related ET200 CPUs and SIPLUS variants): All versions prior to v2.9.2 SIPLUS variants): All versions prior to v4.5.0 Siemens simatic his Pc#
SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl.SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl.SIMATIC Drive Controller family: All versions prior to v2.9.2.SIMATIC S7-1500 Software Controller: All versions prior to v21.9.SIPLUS variants): All versions prior to v21.9 Siemens reports this vulnerability affects the following SIMATIC S7-1200 and S7-1500 CPU products: Successful exploitation of this vulnerability could allow an attacker to write arbitrary data and code to protected memory areas or read sensitive data to launch further attacks. This updated advisory is a follow-up to the original advisory titled ICSA-21-152-01 Siemens SIMATIC S7-1200 and S7-1500 CPU Families that was published June 1, 2021, on the ICS webpage on. Vulnerability: Improper Restriction of Operations within the Bounds of a Memory Buffer.
Equipment: SIMATIC S7-1200 and S7-1500 CPU Families.